List of Parameters
Parameters
1-15
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Filters parameters according to functionality to enable a more focussed approach to commissioning.
Values: 0: All parameters
2: Inverter
3: Motor
4: Speed sensor
5: Technol. application / units
7: Commands, binary I/O
8: AI and AO
10: Setpoint channel / RFG
11: Safety functions
12: Drive features
13: Motor control
19: Motor identification
20: Communication
21: Alarms / warnings / monitoring
22: Technology controller
Description: Selects display for parameter r0000 on OP (drive display).
Example: P0005 = 21: Actual filtered frequency (r0021)
P0005 = 25: Actual output voltage (r0025)
P0005 = 26: Actual filtered DC link voltage (r0026)
P0005 = 27: Actual output current (r0027)
Notice: These settings refer to read only parameter numbers ("rxxxx").
Description: Defines mode of display on OP for r0000 (drive display).
Values: 0: Ready state: setpoint/output frequency. Run: output frequency
1: Ready state: setpoint. Run: output frequency.
2: Ready state: P0005/r0020 value. Run: P0005 value
3: Ready state: r0002/r0020 value. Run: r0002 value
4: In all states just display P0005
Note: When inverter is not running, the display alternates between the values for "Not Running" and "Running".
Per default, the setpoint and actual frequency values are displayed alternately.
p0004 Parameter filter / Parameter filter
CU240S DP-F Access level: 1 P-Group: - Data type: Unsigned16
Quick comm. NO Active: NO Data set: -
Can be changed: U, T
Min Max Factory setting
0 22 0
p0005[0...2] Display selection / Display selection
Access level: 2 P-Group: - Data type: Unsigned16
Quick comm. NO Active: NO Data set: DDS
Can be changed: C, U, T
Min Max Factory setting
2 4000 21
p0006 Display mode / Display mode
Access level: 3 P-Group: - Data type: Unsigned16
Quick comm. NO Active: NO Data set: -
Can be changed: C, U, T
Min Max Factory setting
0 4 2