EasyManua.ls Logo

Siemens Sinamics G120 Series - p1257[0...2] Freq limit for kinetic buffering; Freq limit for KIB; p1300[0...2] Control mode; Control mode

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-150
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Frequency which kinetic buffering (KIB) either hold speed or disable pulses depending on P1256.
Description: Parameter to select the control method.
Controls relationship between speed of motor and voltage supplied by inverter as illustrated in the diagram below.
Values: 0: V/f with linear characteristic
1: V/f with FCC
2: V/f with quadratic characteristic
3: V/f with programmable characteristic
4: reserved
5: V/f for textile applications
6: V/f with FCC for textile applications
19: V/f control with independent voltage setpoint
20: Sensorless vector control
22: Sensorless vector torque-control
Dependency: See parameter P0205, P0500
p1257[0...2] Freq limit for kinetic buffering / Freq limit for KIB
PM240 Access level: 3 P-Group: Setpoints Data type: Floating Point
Quick comm. NO Active: NO Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.00 [Hz] 600.00 [Hz] 2.50 [Hz]
p1300[0...2] Control mode / Control mode
CU240E Access level: 2 P-Group: Closed-loop control Data type: Unsigned16
Quick comm. YES Active: NO Data set: DDS
Can be changed: C, T
Min Max Factory setting
0 22 0
V
n
0
f
n
V
f
V
p1325
f1
p1320
f
max
p1082
V
max
r0071
V
n
p0304
p1323
p1321
p1300 = 0
f0
0 Hz
f2
p1322
f3
p1324
f
n
p0310
f
p1300 = 3
p1310
p1300 = 2

Table of Contents

Related product manuals