Parameters
List of Parameters
1-164
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: If the output current (r0068) exceeds the maximum current (r0067), the frequency inverter is dynamically controlled
by reducing the output voltage. This parameter sets the proportional gain of this controller.
Note: See parameter P1340 for further information.
The Factory setting depends on inverter power.
Description: Integral time constant of the I_max voltage controller.
P1341 = 0 : I_max controller disabled
P1345 = 0 and P1346 > 0 : I_max voltage controller enhanced integral
P1345 > 0 and P1346 > 0 : I_max voltage controller normal PI control
Note: See parameter P1340 for further information.
The Factory setting depends on inverter power.
Description: Sets whether voltage is built up smoothly during magnetization time (ON) or whether it simply jumps to boost volt-
age (OFF).
Values: 0: OFF
1: ON
Note: The settings for this parameter bring benefits and drawbacks:
P1350 = 0: OFF (jump to boost voltage)
Benefit: flux is built up quickly
Drawback: motor may move
P1350 = 1: ON (smooth voltage build-up)
Benefit: motor less likely to move
Drawback: flux build-up takes longer
p1345[0...2] Imax voltage ctrl. prop. gain / Imax volt prp gain
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.000 5.499 0.250
p1346[0...2] Imax voltage ctrl. integral time / Imax volt int time
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.000 [s] 50.000 [s] 0.300 [s]
p1350[0...2] Voltage soft start / Voltage soft start
Access level: 3 P-Group: Closed-loop control Data type: Unsigned16
Quick comm. NO Active: NO Data set: DDS
Can be changed: U, T
Min Max Factory setting
0 1 0