EasyManua.ls Logo

Siemens Sinamics G120 Series - r1912[0...2] Identified stator resistance; Identif. stat. res; r1913[0...2] Identified rotor time constant; Identif.rot.Tconst; r1914[0...2] Ident. total leakage inductance; Tot.leak.induct.; r1915[0...2] Ident. nom. stator inductance; Nom.stat.induct.

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-192
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Displays measured stator resistance value (line-to-line) in [Ohms]. This value also includes the cable resistances.
Index: [0] = U_phase
[1] = V_phase
[2] = W_phase
Notice: If the value identified (Rs = stator resistance) does not lie within the range 0.1 % < Rs [p. u.] < 100 % fault message
41 (motor data identification failure) is issued.
P0949 provides further information (fault value = 2 in this case).
Note: This value is measured using P1900 = 2 or 3 (P1910 = 1 or 2) , i.e., identification of all parameters with/without
change.
Description: Displays identified rotor time constant. [msec]
Index: [0] = U_phase
[1] = V_phase
[2] = W_phase
Notice: If the value identified (Tr = rotor time constant) does not lie within the range 10ms < Tr < 5s fault message 41 (motor
data identification failure) is issued.
P0949 provides further information (fault value = 6 in this case).
Description: Displays identified total leakage inductance. [mH]
Index: [0] = U_phase
[1] = V_phase
[2] = W_phase
Notice: If the value identified (Lsigma = leakage inductance) does not lie within the range 5 % < Xsigma [p. u.] < 50 % fault
message 41 (motor data identification failure) is issued.
P0949 provides further information (fault value = 7 in this case).
Description: Displays identified stator inductance. [mH]
Index: [0] = U_phase
[1] = V_phase
[2] = W_phase
Notice: If the value identified (Ls = stator inductance) does not lie within the range 50 % < Xs [p. u.] < 500 % fault message
41 (motor data identification failure) is issued. P0949 provides further information (fault value = 4 in this case).
Description: Displays identified stator inductance. [mH]
Index: [0] = U_phase
[1] = V_phase
[2] = W_phase
Note: See P1915 (identified nominal stator inductance).
r1912[0...2] Identified stator resistance / Identif. stat. res
Access level: 2 P-Group: Motor identification Data type: Floating Point
Unit: [Ohm] Data set: -
r1913[0...2] Identified rotor time constant / Identif.rot.Tconst
Access level: 2 P-Group: Motor identification Data type: Floating Point
Unit: [ms] Data set: -
r1914[0...2] Ident. total leakage inductance / Tot.leak.induct.
Access level: 2 P-Group: Motor identification Data type: Floating Point
Unit: - Data set: -
r1915[0...2] Ident. nom. stator inductance / Nom.stat.induct.
Access level: 2 P-Group: Motor identification Data type: Floating Point
Unit: - Data set: -
r1916[0...2] Identified stator inductance 1 / Stator induct. 1
Access level: 2 P-Group: Motor identification Data type: Floating Point
Unit: - Data set: -