Description: Defines hysteresis level applied for comparing frequency and speed to threshold as illustrated in the diagram
below.
Description: Selects the source of setpoint frequency, actual frequency is compared with this frequency to detect frequency
deviation (see monitoring bit r2197.7).
Note:
r2131 CO: Last fault number code / Last fault code
Access level: 2 P-Group: Messages Data type: Unsigned16
Unit: - Data set: -
r2132 CO: First warning number code / First warning code
Access level: 2 P-Group: Messages Data type: Unsigned16
Unit: - Data set: -
p2150[0...2] Hysteresis frequency f_hys / Hyst. freq. f_hys
Access level: 3 P-Group: Messages Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.00 [Hz] 10.00 [Hz] 3.00 [Hz]
-1
1
0
0
1
{
-
0
1
{
0
Hyst. freq. f_hys
0.00 ... 10.00 [Hz]
P2150.D (3.00)
Hyst. freq. f_hys
0.00 ... 10.00 [Hz]
P2150.D (3.00)
f_act > 0
| f_act | >= | f_set |
f_act > 0
| f_act| >= | f_set |
f_act
f_set
r2197 Bit03
r0052 Bit14
r2197 Bit04
r0053 Bit06
p2151[0...2] CI: Speed setpoint for messages / n-Set for msg
Access level: 2 P-Group: Messages Data type: Unsigned32
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
- - 1170[0]