EasyManua.ls Logo

Siemens Sinamics G120 Series - p2152[0...2] Delay time of f>fmax; Delay f>fmax; p2153[0...2] Time-constant speed filter; Tconst. speed filt; p2155[0...2] Threshold frequency f_1; Threshold freq f_1; p2156[0...2] Delay time of threshold freq f_1; Delay time of f_1

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-221
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Selects the delay time if actual frequency above maximum frequency.
Note:
Description: Specifies time constant of first-order speed filter.
The filtered speed is then compared to the thresholds.
Note: See diagram in P2155, P2157 and P2159
Description: Sets a threshold for comparing actual speed or frequency to threshold values f_1.
This threshold controls status bits 4 and 5 in status word 2 (r0053).
Description: Sets delay time prior to threshold frequency f_1 comparison (P2155).
Note: See diagram in P2155 (threshold frequency f_1)
p2152[0...2] Delay time of f>fmax / Delay f>fmax
Access level: 2 P-Group: Messages Data type: Unsigned16
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0 [ms] 10000 [ms] 200 [ms]
p2153[0...2] Time-constant speed filter / Tconst. speed filt
Access level: 2 P-Group: Messages Data type: Unsigned16
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0 [ms] 1000 [ms] 5 [ms]
p2155[0...2] Threshold frequency f_1 / Threshold freq f_1
Access level: 3 P-Group: Messages Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.00 [Hz] 650.00 [Hz] 30.00 [Hz]
Tconst. speed filt
0 ... 1000 [ms]
p2153.D (5)
Threshold freq f_1
0.00 ... 650.00 [Hz]
p2155.D (30.00)
Hyst. freq. f_hys
0.00 ... 10.00 [Hz]
p2150.D (3.00)
Delay time of f_1
0 ... 10000 [ms]
p2156.D (10)
Delay time of f_1
0 ... 10000 [ms]
p2156.D (10)
| f_act | <= f_1
| f_act | > f_1
T0
T0
f_act
| f_act | <= f_1
Threshold freq f_1
0.00 ... 650.00 [Hz]
p2155.D (30.00)
Hyst. freq. f_hys
0.00 ... 10.00 [Hz]
p2150.D (3.00)
0
1
{
0
1
{
| f_act | > f_1
r2197 Bit02
r0053 Bit04
r2197 Bit01
r0053 Bit05
r2169
p2156[0...2] Delay time of threshold freq f_1 / Delay time of f_1
Access level: 3 P-Group: Messages Data type: Unsigned16
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0 [ms] 10000 [ms] 10 [ms]

Table of Contents