List of Parameters
Parameters
1-223
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Threshold_3 for comparing speed or frequency to thresholds.
Description: When comparing speed or frequency to threshold f_3 (P2159).
This is the time delay before status bits are set.
Note: See diagram in P2159 (threshold frequency f_3)
p2159[0...2] Threshold frequency f_3 / Threshold freq f_3
Access level: 2 P-Group: Messages Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.00 [Hz] 650.00 [Hz] 30.00 [Hz]
Tconst. speed filt
0 ... 1000 [ms]
P2153.D (5)
Threshold freq f_3
0.00 ... 650.00 [Hz]
P2159.D (30.00)
Hyst. freq. f_hys
0.00 ... 10.00 [Hz]
P2150.D (3.00)
Delay time of f_3
0 ... 10000 [ms]
P2160.D (10)
Delay time of f_3
0 ... 10000 [ms]
P2160.D (10)
| f_act | <= f_3
| f_act | > f_3
T0
T0
f_act
r2198 Bit03
r2198 Bit02
| f_act | <= f_3
Threshold freq f_3
0.00 ... 650.00 [Hz]
P2159.D (30.00)
Hyst. freq. f_hys
0.00 ... 10.00 [Hz]
P2150.D (3.00)
0
1
{
0
1
{
| f_act | > f_3
r2169
p2160[0...2] Delay time of threshold freq f_3 / Delay time of f_3
Access level: 2 P-Group: Messages Data type: Unsigned16
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0 [ms] 10000 [ms] 10 [ms]