EasyManua.ls Logo

Siemens Sinamics G120 Series - p2172[0...2] Threshold DC-link voltage; Vdc threshold; p2173[0...2] Delay time DC-link voltage; Vdc delay time

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-229
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Defines DC link voltage to be compared to actual voltage as illustrated in the diagram below.
Note: This voltage controls bits 7 and 8 in status word 3 (r0053).
Description: Defines delay time prior to activation of threshold comparison.
Note: See diagram in P2172 (threshold DC-link voltage)
p2172[0...2] Threshold DC-link voltage / Vdc threshold
Access level: 3 P-Group: Messages Data type: Unsigned16
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0 [V] 2000 [V] 800 [V]
V
dc
t
0
1
0
1
p2173
t
t
r0053
Bit07
r0053
Bit08
p2172
p2173
V
dc_act
< p2172
V
dc_act
> p2172
p2173[0...2] Delay time DC-link voltage / Vdc delay time
Access level: 3 P-Group: Messages Data type: Unsigned16
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0 [ms] 10000 [ms] 10 [ms]

Table of Contents