SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Displays measured heatsink temperature and calculated junction temperature of IGBTs based on thermal model.
Index: [0] = Measured heat sink temperature
[1] = Total Chip Junction Temperature
Note: The values are updated every 128 ms.
Description: Displays the filtered power factor.
Description: Displays electrical energy used by inverter since display was last reset (see P0040 - reset energy consumption
meter).
Dependency: Value is reset when P0040 = 1 (reset energy consumption meter).
Description: Resets value of parameter r0039 (energy consumption meter) to zero.
Values: 0: No reset
1: Reset r0039 to 0
Description: Displays currently active Command Dataset (CDS).
Values: 0: Command Dataset 0 (CDS)
1: Command Dataset 1 (CDS)
2: Command Dataset 2 (CDS)
Note: See parameter P0810.
Description: Displays currently selected and active Drive Dataset (DDS).
Values: 0: Drive Dataset 0 (DDS0)
1: Drive Dataset 1 (DDS1)
2: Drive Dataset 2 (DDS2)
Index: [0] = Selected Drive Dataset
[1] = Active Drive Dataset
Note: See parameter P0820.
r0037[0...1] CO: Inverter temperature [°C] / Inverter temp.
Access level: 3 P-Group: Converter Data type: Floating Point
Unit: [°C] Data set: -
r0038 CO: Fil. power factor / Fil.power fact
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Unit: - Data set: -
r0039 CO: Energy consumpt. meter [kWh] / Energy meter
Access level: 2 P-Group: Converter Data type: Floating Point
Unit: [kWh] Data set: -
p0040 Reset energy consumption meter / Reset energy meter
Access level: 2 P-Group: Converter Data type: Unsigned16
Quick comm. NO Active: NO Data set: -
Can be changed: T
Min Max Factory setting
0 1 0
r0050 CO/BO: Active Command Dataset / Active CDS
Access level: 2 P-Group: Commands Data type: Unsigned16
Unit: - Data set: -
r0051[0...1] CO: Active Drive Dataset (DDS) / Active DDS
Access level: 2 P-Group: Commands Data type: Unsigned16
Unit: - Data set: -