EasyManua.ls Logo

Siemens Sinamics G120 Series - p2190[0...2] Lower torque threshold 3; Lower trq. thresh3; p2192[0...2] Time delay for belt failure; Belt fail delay_T; r2197.0...12 CO;BO: Monitoring word 1; Monitor Wd1

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-235
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Lower limit threshold value 3 for comparing actual torque.
Note: See P2182 (belt threshold frequency 1).
Description: P2192 defines a delay before warning/trip becomes active.
It is used to eliminate events caused by transient conditions.
It is used for both methods of fault detection.
Description: Monitoring word 1 which indicates the state of monitor functions.
Each bit represents one monitor function.
p2190[0...2] Lower torque threshold 3 / Lower trq. thresh3
Access level: 2 P-Group: Messages Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.0 [Nm] 99999.0 [Nm] 0.0 [Nm]
p2192[0...2] Time delay for belt failure / Belt fail delay_T
Access level: 2 P-Group: Messages Data type: Unsigned16
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0 [s] 65 [s] 10 [s]
r2197.0...12 CO/BO: Monitoring word 1 / Monitor Wd1
PM240 Access level: 2 P-Group: Messages Data type: Unsigned16
Unit: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 f_act <= P1080 (f_min) Yes No -
01 f_act <= P2155 (f_1) Yes No -
02 f_act > P2155 (f_1) Yes No -
03 f_act > zero Yes No -
04 f_act >= setp. (f_set) Yes No -
05 f_act <= P2167 (f_off) Yes No -
06 f_act >= P1082 (f_max) Yes No -
07 f_act == setp. (f_set) Yes No -
08 Act. current r0068 <= P2170 Yes No -
09 Act. unfilt. Vdc < P2172 Yes No -
10 Act. unfilt. Vdc > P2172 Yes No -
11 Load missing Yes No -
12 f_act > P1082 with delay Yes No -

Table of Contents