Description: Selects mode of timer 4.
P2864, P2865, P2866 are the inputs of the timer, outputs are P2867, P2868.
Values: 0: ON delay (seconds)
1: OFF delay (seconds)
2: ON/OFF delay (seconds)
3: Pulse generator (seconds)
10: ON delay (minutes)
11: OFF delay (minutes)
12: ON/OFF delay (minutes)
13: Pulse generator (minutes)
Dependency: P2802[3] is active level for the timer.
Description: Displays output of timer 4.
P2864, P2865, P2866 are the inputs of the timer, outputs are P2867, P2868.
Dependency: P2802[3] is active level for the timer.
Description: Displays Not-output of timer 4.
P2864, P2865, P2866 are the inputs of the timer, outputs are P2867, P2868.
Dependency: P2802[3] is active level for the timer.
Description: Define inputs of Adder 1, result is in P2870.
Index: [0] = Connector input 0 (CI 0)
[1] = Connector input 1 (CI 1)
Dependency: P2802[4] is the active level for the Adder.
p2866 Mode timer 4 / Mode timer 4
Access level: 3 P-Group: Technology Data type: Unsigned16
Quick comm. NO Active: NO Data set: -
Can be changed: U, T
Min Max Factory setting
0 13 0
r2867.0 BO: Timer 4 / Timer 4
Access level: 3 P-Group: Technology Data type: Unsigned16
Unit: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Output of BO Yes No -
r2868.0 BO: Nout timer 4 / Nout timer 4
Access level: 3 P-Group: Technology Data type: Unsigned16
Unit: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Output of BO Yes No -
p2869[0...1] CI: ADD 1 / ADD 1
Access level: 3 P-Group: Technology Data type: Unsigned32
Quick comm. NO Active: NO Data set: -
Can be changed: U, T
Min Max Factory setting
- - 755[0]
r2870
x1
x2
200%
-200%
p2800
p2802[4]
Result = x1 + x2
If:
x1 + x2 > 200%
x1 + x2 < -200%
Result = 200%
Result = -200%
Result
p2869
x1 + x2
Index0
Index1