Parameters
List of Parameters
1-30
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Displays maximum output voltage.
Dependency: Actual maximum output voltage depends on the actual input supply voltage.
Description: Displays output voltage. This value is available filtered (r0025) and unfiltered (r0072).
Description: Displays actual modulation index.
The modulation index is defined as ratio between the magnitude of the fundamental component in the inverter
phase output voltage and half of the DC-link voltage.
Description: Displays setpoint of flux generating current component.
Dependency: Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero.
Description: Displays flux generating current component. This value is available filtered (r0029) and unfiltered (r0076).
Dependency: Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero.
Description: Displays setpoint for component of torque generating current.
Dependency: Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero.
Description: Displays component of torque generating current. This value is available filtered (r0030) and unfiltered (r0078).
Description: Displays total torque setpoint after limitation.
Dependency: Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero.
r0071 CO: Max. output voltage / Max. outp.volt
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Unit: [V] Data set: -
r0072 CO: Act. output voltage / Act. outp.volt
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Unit: [V] Data set: -
r0074 CO: Act. modulation / Act modulation
Access level: 4 P-Group: Closed-loop control Data type: Floating Point
Unit: [%] Data set: -
r0075 CO: Current setpoint Isd / Cur. setp. Isd
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Unit: [A] Data set: -
r0076 CO: Act. current Isd / Act. cur. Isd
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Unit: [A] Data set: -
r0077 CO: Current setpoint Isq / Cur. setp. Isq
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Unit: [A] Data set: -
r0078 CO: Act. current Isq / Act. cur. Isq
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Unit: [A] Data set: -
r0079 CO: Torque setpoint (total) / Total trq setp
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Unit: [Nm] Data set: -