F00004 Inverter Over Temperature
Reaction: OFF 2
Acknowledge: Quit fault eg. via DI2
Cause: Inverter overloaded
Ventilation inadequate
Pulse frequency too high
Ambient temperature too high
Fan inoperative
Remedy: Check the following:
Load or load cycle too high?
Motor power (p0307) must match inverter power (r0206)
Pulse frequency must be set to default value
Ambient temperature too high?
Fan must turn when inverter is running
F00005 Inverter I2T
Reaction: OFF 2
Acknowledge: Quit fault eg. via DI2
Cause: Inverter overloaded.
Load cycle too demanding.
Motor power (p0307) exceeds inverter power capability (r0206).
Remedy: Check the following:
Load cycle must lie within specified limits.
Motor power (p0307) must match inverter power (r0206)
F00006 Chip temperature rise exceeds critical levels.
Reaction: OFF 2
Acknowledge: Quit fault eg. via DI2
Cause: Load at start-up is too high
Load step is too high
Ramp-up rate is too fast
Remedy: Check the following:
Load or load step too high?
Reduce ramp-up time (P1120).
Motor power (p0307) must match inverter power (r0206).
Use setting P0290 = 0 or 2 for preventing F00006.
F00011 Motor Over Temperature
Reaction: OFF 2 (OFF 3)
Acknowledge: Quit fault eg. via DI2
Cause: Motor overloaded
Remedy: Check the following:
Load or load step too high?
Motor nominal overtemperatures (p0626 - p0628) must be correct
Motor temperature warning level (p0604) must match