A00705 PROFIBUS: timeout actual value
Reaction: NONE
Acknowledge: NONE
Cause: no actual data from CUP
Remedy: temporary, if permanent the fault detection is activated
A00706 PROFIBUS: fatal SW error (e.g. hardware check, communication, V
Reaction: NONE
Acknowledge: NONE
Cause: e.g. hardware check, communication, V1SL stack, ...
Remedy: if permanent power cycle, reload firmware
A00707 PROFIBUS: wrong PB address at startup
Reaction: NONE
Acknowledge: NONE
Cause: wrong DIP switch or parameter settings for PROFIBUS address
Remedy: check DIP switch and/or P0918
A00708 --- not used ---
Reaction: NONE
Acknowledge: NONE
Cause:
Remedy:
A00709 --- not used ---
Reaction: NONE
Acknowledge: NONE
Cause:
Remedy:
A00710 CB communication error
Reaction: NONE
Acknowledge: NONE
Cause: Communication with CB (communication board) is lost.
Remedy: Check CB hardware
A00711 CB configuration error
Reaction: NONE
Acknowledge: NONE
Cause: CB (communication board) reports a configuration error.
Remedy: Check CB parameters
A00910 Vdc-max controller de-activated
Reaction: NONE
Acknowledge: NONE
Cause: Occurs
if main supply voltage (P0210) is permanently too high.
if motor is driven by an active load, causing motor to goes into regenerative mode.
at very high load inertias, when ramping down.
Remedy: Check the following:
Input voltage must lie within range.
Load must be match.
In certain cases apply braking resistor.