Faults and Alarms
List of Fault and Alarm messages
3-396
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
A00911 Vdc-max controller active
Reaction: NONE
Acknowledge: NONE
Cause: Vdc max controller is active; so ramp-down times will be increased automatically to keep DC-link voltage (r0026)
within limits (P2172).
Remedy: Check the following:
Supply voltage must lie within limits indicated on rating plate.
Ramp-down time (P1121) must match inertia of load.
Note: Higher inertia requires longer ramp times; otherwise, apply braking resistor.
A00912 Vdc-min Controller active
Reaction: NONE
Acknowledge: NONE
Cause: Vdc min controller will be activated if DC-link voltage (r0026) falls below minimum level (P2172).
The kinetic energy of the motor is used to buffer the DC-link voltage, thus causing deceleration of the drive! So short
mains failures do not necessarily lead to an undervoltage trip.
Remedy:
A00921 AO parameters not set properly.
Reaction: NONE
Acknowledge: NONE
Cause: AO parameters (P0777 and P0779) should not be set to identical values, since this would produce illogical results.
Remedy: Check the following:
Parameter settings for output identical
Parameter settings for input identical
Parameter settings for output do not correspond to AO type
Set P0777 and P0779 to different values.
A00922 No load applied to inverter
Reaction: NONE
Acknowledge: NONE
Cause: No Load is applied to the inverter.
As a result, some functions may not work as under normal load conditions.
Remedy: Check that motor is connected to inverter.
A00923 Both JOG Left and JOG Right are requested
Reaction: NONE
Acknowledge: NONE
Cause: Both JOG right and JOG left (P1055/P1056) have been requested. This freezes the RFG output frequency at its cur-
rent value.
Remedy: Do not press JOG right and left simulutanously.
A00936 PID Autotuning Active
Reaction: NONE
Acknowledge: NONE
Cause: PID Autotuning (P2350) selected or running
Remedy: Alarm disappears when PID Autotuning has finished.