EasyManua.ls Logo

Siemens Sinamics G120 Series - p0311[0...2] Rated motor speed; Rated motor speed; r0313[0...2] Motor pole pairs; Motor pole pairs; p0314[0...2] Motor pole pair number; Motor pole pair no; p0320[0...2] Motor magnetizing current; Motor magnet. cur.

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-45
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Nominal motor speed [rpm] from rating plate - see P0304.
Dependency: Changeable only when P0010 = 1 (quick commissioning).
Setting 0 causes internal calculation of value.
Required for vector control and V/f control with speed controller.
Slip compensation in V/f control requires rated motor speed for correct operation.
Pole pair number recalculated automatically if parameter is changed.
Note: Default value is depending on inverter type and its rating data.
Description: Displays number of motor pole pairs that the inverter is currently using for internal calculations.
Dependency: Recalculated automatically when P0310 (rated motor frequency) or P0311 (rated motor speed) is changed.
r0313 = 1 : 2-pole motor
r0313 = 2 : 4-pole motor
etc.
Description: Specifies number of pole pairs of motor.
Dependency: Changeable only when P0010 = 1 (quick commissioning).
Setting 0 causes r0313 (calculated motor pole pairs) to be used during operation. Setting to > 0 overrides r0313.
P0314 = 1 : 2-pole motor
P0314 = 2 : 4-pole motor
etc.
Description: Defines motor magnetization current in [%] relative to P0305 (rated motor current).
Dependency: Setting 0 causes calculation by P0340 = 1 (data entered from rating plate) or by P3900 = 1 - 3 (end of quick com-
missioning). The calculated value is displayed in parameter r0331.
p0311[0...2] Rated motor speed / Rated motor speed
Access level: 1 P-Group: Motor Data type: Unsigned16
Quick comm. YES Active: NO Data set: DDS
Can be changed: C
Min Max Factory setting
0 [RPM] 40000 [RPM] 1395 [RPM]
r0313[0...2] Motor pole pairs / Motor pole pairs
Access level: 3 P-Group: Motor Data type: Unsigned16
Unit: - Data set: DDS
p0314[0...2] Motor pole pair number / Motor pole pair no
Access level: 3 P-Group: Motor Data type: Unsigned16
Quick comm. YES Active: NO Data set: DDS
Can be changed: C
Min Max Factory setting
0 99 0
p0320[0...2] Motor magnetizing current / Motor magnet. cur.
Access level: 3 P-Group: Motor Data type: Floating Point
Quick comm. YES Active: YES Data set: DDS
Can be changed: C, T
Min Max Factory setting
0.0 [%] 99.0 [%] 0.0 [%]