Description: Selects function of digital input 5.
Values: 0: Digital input disabled
1: ON/OFF1
2: ON reverse /OFF1
3: OFF2 - coast to standstill
4: OFF3 - quick ramp-down
9: Fault acknowledge
10: JOG right
11: JOG left
12: Reverse
13: MOP up (increase frequency)
14: MOP down (decrease frequency)
15: Fixed frequency selector bit0
16: Fixed frequency selector bit1
17: Fixed frequency selector bit2
18: Fixed frequency selector bit3
27: Enable PID
29: External trip
33: Disable additional freq setpoint
99: Enable BICO parameterization
Note: See P0701 (function of digital input 0).
Description: Selects function of digital input 6.
Values: 0: Digital input disabled
1: ON/OFF1
2: ON reverse /OFF1
3: OFF2 - coast to standstill
4: OFF3 - quick ramp-down
9: Fault acknowledge
10: JOG right
11: JOG left
12: Reverse
13: MOP up (increase frequency)
14: MOP down (decrease frequency)
15: Fixed frequency selector bit0
16: Fixed frequency selector bit1
17: Fixed frequency selector bit2
18: Fixed frequency selector bit3
25: DC brake enable
27: Enable PID
29: External trip
33: Disable additional freq setpoint
99: Enable BICO parameterization
Note: See P0701 (function of digital input 0).
p0706[0...2] Function of digital input 5 / Function of DI5
PM250
PM260
Access level: 2 P-Group: Commands Data type: Unsigned16
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
0 99 17
p0707[0...2] Function of digital input 6 / Function of DI6
CU240S
CU240S DP
CU240S PN
PM240
Access level: 2 P-Group: Commands Data type: Unsigned16
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
0 99 18