EasyManua.ls Logo

Siemens Sinamics G120 Series - p0709[0...2] Function of digital input 8; Function of DI8; p0712[0...2] Analog; digital input 0; Ana;digi input 0

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-76
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Values: 0: Digital input disabled
1: ON/OFF1
2: ON reverse /OFF1
3: OFF2 - coast to standstill
4: OFF3 - quick ramp-down
9: Fault acknowledge
10: JOG right
11: JOG left
12: Reverse
13: MOP up (increase frequency)
14: MOP down (decrease frequency)
15: Fixed frequency selector bit0
16: Fixed frequency selector bit1
17: Fixed frequency selector bit2
18: Fixed frequency selector bit3
27: Enable PID
29: External trip
33: Disable additional freq setpoint
99: Enable BICO parameterization
Note: See P0701 (function of digital input 0).
Description: Selects function of digital input AI0 (via analog input)
Values: 0: Digital input disabled
1: ON/OFF1
2: ON reverse /OFF1
3: OFF2 - coast to standstill
4: OFF3 - quick ramp-down
9: Fault acknowledge
10: JOG right
11: JOG left
12: Reverse
13: MOP up (increase frequency)
14: MOP down (decrease frequency)
15: Fixed frequency selector bit0
16: Fixed frequency selector bit1
17: Fixed frequency selector bit2
18: Fixed frequency selector bit3
25: DC brake enable
27: Enable PID
29: External trip
33: Disable additional freq setpoint
99: Enable BICO parameterization
Note: See P0701 (function of digital input 0).
Signals above 4 V are active, signals below 1,6 V are inactive.
p0709[0...2] Function of digital input 8 / Function of DI8
CU240S
CU240S DP
CU240S PN
PM250, PM260
Access level: 2 P-Group: Commands Data type: Unsigned16
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
0 99 0
p0712[0...2] Analog / digital input 0 / Ana/digi input 0
PM240 Access level: 2 P-Group: Commands Data type: Unsigned16
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
0 99 0

Table of Contents

Related product manuals