List of Parameters
Parameters
1-79
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Central switch to select control command source for inverter.
Switches command and setpoint source between freely programmable BICO parameters and fixed command/set-
point profiles.
Command and setpoint sources can be changed independently.
The tens digit chooses the command source and the units digit chooses the setpoint source.
Values: 0: Cmd = BICO parameter Setpoint = BICO parameter
1: Cmd = BICO parameter Setpoint = MOP setpoint
2: Cmd = BICO parameter Setpoint = Analog setpoint
3: Cmd = BICO parameter Setpoint = Fixed frequency
4: Cmd = BICO parameter Setpoint = USS on RS232
5: Cmd = BICO parameter Setpoint = USS on RS485
7: Cmd = BICO parameter Setpoint = Analog setpoint 2
10: Cmd = BOP Setpoint = BICO parameter
11: Cmd = BOP Setpoint = MOP setpoint
12: Cmd = BOP Setpoint = Analog setpoint
13: Cmd = BOP Setpoint = Fixed frequency
14: Cmd = BOP Setpoint = USS on RS232
15: Cmd = BOP Setpoint = USS on RS485
17: Cmd = BOP Setpoint = Analog setpoint 2
40: Cmd = USS on RS232 Setpoint = BICO parameter
41: Cmd = USS on RS232 Setpoint = MOP setpoint
42: Cmd = USS on RS232 Setpoint = Analog setpoint
43: Cmd = USS on RS232 Setpoint = Fixed frequency
44: Cmd = USS on RS232 Setpoint = USS on RS232
45: Cmd = USS on RS232 Setpoint = USS on RS485
47: Cmd = USS on RS232 Setpoint = Analog setpoint 2
50: Cmd = USS on RS485 Setpoint = BICO parameter
51: Cmd = USS on RS485 Setpoint = MOP setpoint
52: Cmd = USS on RS485 Setpoint = Analog setpoint
53: Cmd = USS on RS485 Setpoint = Fixed frequency
54: Cmd = USS on RS485 Setpoint = USS on RS232
55: Cmd = USS on RS485 Setpoint = USS on RS485
57: Cmd = USS on RS485 Setpoint = Analog setpoint 2
Dependency: P0719 has higher priority than P0700 and P1000.
If set to a value other than 0 (i.e. BICO parameter is not the setpoint source), P0844 / P0848 (first source of OFF2 /
OFF3) are not effective; instead, P0845 / P0849 (second source of OFF2 / OFF3) apply and the OFF commands
are obtained via the particular source defined.
BICO connections made previously remain unchanged.
Notice: Particularly useful when e.g. changing command source temporarily from P0700 = 2.
Settings in P0719 (contrary to P0700 settings) do not reset the digital inputs (P0701, P0702, ...)
p0719[0...2] Selection of cmd. & freq. setp. / Cmd.&freq.setp.sel
CU240E
CU240S
Access level: 4 P-Group: Commands Data type: Unsigned16
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
0 57 0