List of Parameters
Parameters
1-81
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Displays number of digital inputs.
Description: Displays status of digital inputs.
Note: Segment is lit when signal is active.
Description: Displays status of digital inputs.
Note: Segment is lit when signal is active.
Description: Defines debounce time (filtering time) used for digital inputs.
Values: 0: No debounce time
1: 2.5 ms debounce time
2: 8.2 ms debounce time
3: 12.3 ms debounce time
r0720 Number of digital inputs / Number of DI
Access level: 3 P-Group: Commands Data type: Unsigned16
Unit: - Data set: -
r0722.0...12 CO/BO: Binary input values / Bin.inp.val
CU240E
CU240S DP-F
Access level: 2 P-Group: Commands Data type: Unsigned16
Unit: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Digital input 0 Yes No -
01 Digital input 1 Yes No -
02 Digital input 2 Yes No -
03 Digital input 3 Yes No -
04 Digital input 4 Yes No -
05 Digital input 5 Yes No -
11 Digital input AI0 Yes No -
12 Digital input AI1 Yes No -
r0722.0...12 CO/BO: Binary input values / Bin.inp.val
CU240S
CU240S DP
CU240S PN
Access level: 2 P-Group: Commands Data type: Unsigned16
Unit: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Digital input 0 Yes No -
01 Digital input 1 Yes No -
02 Digital input 2 Yes No -
03 Digital input 3 Yes No -
04 Digital input 4 Yes No -
05 Digital input 5 Yes No -
06 Digital input 6 Yes No -
07 Digital input 7 Yes No -
08 Digital input 8 Yes No -
11 Digital input AI0 Yes No -
12 Digital input AI1 Yes No -
p0724 Debounce time for digital inputs / Debounce time: DI
Access level: 3 P-Group: Commands Data type: Unsigned16
Quick comm. NO Active: YES Data set: -
Can be changed: T
Min Max Factory setting
0 3 3