EasyManua.ls Logo

Siemens Sinamics G120 Series - p0753[0...1] Smooth time AI; Smooth time AI; r0754[0...1] Act. AI value after scaling [%]; AI after scal.[%]; r0755[0...1] CO: Act. AI after scal. [4000 h]; CO:AI scal[4000 h]

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-85
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Defines filter time (PT1 filter) in [ms] for analog input.
Index: [0] = Analog input 0 (AI0)
[1] = Analog input 1 (AI1)
Note: Increasing this time (smooth) reduces jitter but slows down response to the analog input.
P0753 = 0 : No filtering
Description: Shows smoothed value of analog input in [%] after scaling block.
Index: [0] = Analog input 0 (AI0)
[1] = Analog input 1 (AI1)
Dependency: P0757 to P0760 define range (AI scaling).
Description: Displays analog input, scaled using ASPmin and ASPmax (ASP = analog setpoint).
Analog setpoint (ASP) from the analog scaling block can vary from min. analog setpoint (ASPmin) to a max. analog
setpoint (ASPmax).
The largest magnitude (value without sign) of ASPmin and ASPmax defines the scaling of 16384.
By associating parameter r0755 with an internal value (e.g. frequency setpoint), a scaled value is calculated inter-
nally by the inverter.
The frequency value is calculated using the following equation:
Example: Case a:
ASPmin = 300 %, ASPmax = 100 % then 16384 represents 300 %.
This parameter will vary from 5461 to 16384.
Case b:
ASPmin = -200 %, ASPmax = 100 % then 16384 represents 200 %.
This parameter will vary from -16384 to +8192.
p0753[0...1] Smooth time AI / Smooth time AI
Access level: 3 P-Group: Terminals Data type: Unsigned16
Quick comm. NO Active: NO Data set: -
Can be changed: U, T
Min Max Factory setting
0 [ms] 10000 [ms] 3 [ms]
r0754[0...1] Act. AI value after scaling [%] / AI after scal.[%]
Access level: 2 P-Group: Terminals Data type: Floating Point
Unit: [%] Data set: -
r0755[0...1] CO: Act. AI after scal. [4000h] / CO:AI scal[4000h]
Access level: 2 P-Group: Terminals Data type: Integer16
Unit: - Data set: -
100%
)ASP ,ASP(max
2000p
[Hex] 4000
[Hex] r0755
[Hz] r0755
minmax
=
AI
r0755 [Hex] r0755 [Hz]
ASP
max
10 V
V
%
ASP
min