EasyManua.ls Logo

Siemens Sinamics G120 Series - p0803 Transfer data to EEPROM; Transf.Ext->Drive; p0804 Select Clone file; Select Clone file; p0806 BI: Inhibit panel access; Inhibit panel acce

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-93
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Transfers values from External to drive when none 0.
Parameter P0010 must be set to 30 for this to be possible.
Values: 0: Disabled
1: Start OP Transfer
Note: Parameter is automatically reset to 0 (default) after transfer.
P0010 will be reset to 0 on successful completion.
Description: Transfers values from External to drive when none 0.
Parameter P0010 must be set to 30 for this to be possible.
Values: 0: Disabled
1: Start OP Transfer
2: Start MMC Transfer
Note: Parameter is automatically reset to 0 (default) after transfer.
P0010 will be reset to 0 on successful completion.
Description: Select clone file to up/down load.
if P0804 = 0 then file name is clone00.bin
if P0804 = 1 then file name is clone01.bin
etc.
Description: Binector input to lock control panel access through external client.
p0803 Transfer data to EEPROM / Transf.Ext->Drive
CU240E Access level: 3 P-Group: Factory settings Data type: Unsigned16
Quick comm. NO Active: NO Data set: -
Can be changed: -
Min Max Factory setting
0 1 0
p0803 Transfer data to EEPROM / Transf.Ext->Drive
CU240S
CU240S DP
CU240S DP-F
CU240S PN
Access level: 3 P-Group: Factory settings Data type: Unsigned16
Quick comm. NO Active: NO Data set: -
Can be changed: -
Min Max Factory setting
0 2 0
p0804 Select Clone file / Select Clone file
CU240S
CU240S DP
CU240S DP-F
CU240S PN
Access level: 3 P-Group: Factory settings Data type: Unsigned16
Quick comm. NO Active: NO Data set: -
Can be changed: -
Min Max Factory setting
0 99 0
p0806 BI: Inhibit panel access / Inhibit panel acce
Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: YES Data set: -
Can be changed: U, T
Min Max Factory setting
- - 0

Table of Contents