List of Parameters
Parameters
1-97
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Allows ON/OFF1 reverse command source to be selected using BICO.
In general a positive frequency setpoint is run up counterclockwise (negative frequency).
Description: Defines first source of OFF2 when P0719 = 0 (BICO).
Dependency: If one of the digital inputs is selected for OFF2, the inverter will not run unless the digital input is active.
When Standard Telegram selected (p0700 = 6, p0922 = Standard Telegram), parameter cannot be changed.
Note: OFF2 means immediate pulse-disabling; the motor is coasting.
OFF2 is low-active, i.e. :
0 = Pulse disabling.
1 = Operating condition.
Description: Defines first source of OFF2 when P0719 = 0 (BICO).
Dependency: If one of the digital inputs is selected for OFF2, the inverter will not run unless the digital input is active.
When Standard Telegram selected (p0700 = 6, p0922 = Standard Telegram), parameter cannot be changed.
Note: OFF2 means immediate pulse-disabling; the motor is coasting.
OFF2 is low-active, i.e. :
0 = Pulse disabling.
1 = Operating condition.
p0842[0...2] BI: ON reverse/OFF1 / BI:ON reverse/OFF1
Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 0
p0844[0...2] BI: 1. OFF2 / 1. OFF2
CU240E
CU240S
Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 1
p0844[0...2] BI: 1. OFF2 / 1. OFF2
CU240S DP
CU240S DP-F
Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 2090.1