EasyManua.ls Logo

Siemens SINAMICS G120 - Page 163

Siemens SINAMICS G120
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Accessories
8.12 dv/dt filter plus VPL
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
161
Article number JTA: TEF1203
-0GB
-0HB
-0JB
Voltage drop
17.15 V
17.13 V
17.97 V
Rated DC link voltage
935 V
935 V
935 V
Maximum voltage rise at motor ter-
minals
1)
< 500 V/μs < 500 V/μs < 500 V/μs
Maximum peak voltage at motor
terminals (phase to phase)
2)
1350 V 1350 V 1350 V
Maximum peak voltage at motor
terminals (phase to earth)
2)
1100 V 1100 V 1100 V
Maximum cable length filter - motor
(screened / unscreened)
350 m / 525 m 350 m / 525 m 350 m / 525 m
Terminal type
Screw terminals
Screw terminals
Screw terminals
Rated terminal cross section (load
circuit)
16 mm² 35 mm² 50 m
Rated terminal cross section (DC
link feedback)
3)
16 mm² 16 mm² 16 mm²
Degree of protection
4)
IP00
IP00
IP00
Ambient temperature
5)
-20°C to 40°C
-20°C to 40°C
-20°C to 40°C
Weight
20 kg
29 kg
46 kg
Connection Metrical (mm² / Nm)
Imperial (AWG / lbf.in)
Stripping length (mm)
Line / motor cable 16 / 1.2
6 / 11.0
13
35 / 2.5
2 / 22
17
70 / 6.0
2/0 / 53
24
DC link 16 / 1.2
6 / 11.0
13
16 / 1.2
6 / 11
13
16 / 1.2
6 / 11
13
Ground 16 / 1.2
6 / 11.0
13
35 / 2.5
2 / 22
17
70 / 10.0
2/0 / 86
24
1)
Voltage rise according IEC/TS 60034-17
2)
Under nominal DC link voltage
3)
Short-circuit-proof wiring is required
4)
Installing the filter in an enclosure is required
5)
Higher ambient temperatures up to 60°C allowed with current derating at 40°C, in the range 4050°C with 1.5% per 1K
and in the range 5060°C with 1.9% per 1K

Table of Contents

Other manuals for Siemens SINAMICS G120

Related product manuals