Configuring the fieldbus
7.6 Communication via RS485
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
167
On/Off text
or value range
40407 Failure number, index 6 R -- 1 0 … 32767 r0947 [7]
40499 PRM ERROR code R -- 1 0 …99 --
Technology controller enable
Technology controller MOP
Technology controller adjustment
40510 Time constant for actual-value filters
of the technology controller
R/W -- 100 0.00 … 60.0 p2265
40511 Scaling factor for actual value of the
R/W % 100 0.00 … 500.00 p2269
40512 Proportional amplification of the
R/W -- 1000 0.000 … 65.000 p2280
40513 Integral time of the technology
R/W s 1 0 … 60 p2285
40514 Time constant D-component of the
R/W -- 1 0 … 60 p2274
Max. limit of technology controller
Min. limit technology controller
40520 Effective setpoint acc. to internal
technology controller MOP ramp-
R % 100 -100.0 … 100.0 r2250
40521 Actual value of technology controller
R % 100 -100.0 … 100.0 r2266
Output signal technology controller