Configuring the fieldbus
7.6 Communication via RS485
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
181
AV5105 INTEG TIME 0 Technology controller 0 integral
s 0 … 1000 W p11085
AV5106 OUTPUT MAX 0 Technology controller 0
% - 200 … 200 W p11091
AV5107 OUTPUT MIN Technology controller 0
% - 200 … 200 W p11092
AV5200 RAMP UP TIME 1 Technology controller 1 ramp-up
s 0 … 650 W p11157
AV5201 RAMP DOWN TIME 1 Technology controller 1 ramp-
s 0 … 650 W p11158
AV5202 FILTER TIME 1 Technology controller 1 actual
value filter time constant
s 0 … 60 W p11165
AV5203 DIFF TIME 1 Technology controller 1
differentiation time constant
s 0 … 60 W p11174
AV5204 PROP GAIN 1 Technology controller 1
s 0 … 1000 W p11180
AV5205 INTEG TIME 1 Technology controller integral
time
s 0 … 1000 W p11185
AV5206 OUTPUT MAX 1 Technology controller 1
% - 200 … 200 W p11191
AV5207 OUTPUT MIN 1 Technology controller 1
% - 200 … 200 W p11192
AV5300 RAMP UP TIME 2 Technology controller 2 ramp-up
s 0 … 650 W p11257
AV5301 RAMP DOWN TIME 2 Technology controller 2 ramp-
s 0 … 650 W p11258
AV5302 FILTER TIME 2 Technology controller 2 actual
value filter time constant
s 0 … 60 W p11265
AV5303 DIFF TIME 2 Technology controller 2
differentiation time constant
s 0 … 60 W p11274
AV5304 PROP GAIN 2 Technology controller 2
s 0 … 1000 W p11280
AV5305 INTEG TIME 2 Technology controller 2 integral
s 0 … 1000 W p11285
AV5306 OUTPUT MAX 2 Technology controller 2
% - 200 … 200 W p11291
AV5307 OUTPUT MIN 2 Technology controller 2
% - 200 … 200 W p11292