Setting functions
8.7 Application-specific functions
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
307
Table 8- 33 Order of deactivation for external motors depending on setting in p2371
If you are using motors of the same power rating, you can use p2372 to define whether the
motors are to be activated/deactivated following the setting specified in p2371 (p2372 = 0) or
based on the operating hours (p2372 = 1, 2 ,3. Details see parameter list).
Parameters to set and activate the cascade control:
p0730 = r2379.0
Signal source for digital output 0
Control external motor 1 via DO 0
p0731 = r2379.1
Signal source for digital output 1
Control external motor 2 via DO 1
p0732 = r2379.2
Signal source for digital output 2
Control external motor 3 via DO 2
p2200 = 1
Technology controller release
Activate technology controller
p2251 = 0
Technology controller mode
Technology controller as main speed setpoint
p2370
Signal source for staging on/off
Cascade control- configuration Activate staging and define switch-on sequence
p2372
Cascade control - motor selection mode
Define automatic motor switch-on
p2373
Cascade control - switch-in threshold
Define switch-on threshold
p2374
-
switch-in delay
Define delay time
p2375
Cascade control switch-off delay
Define delay time for de-staging
p2376
Cascade control - overcontrol threshold
Define overcontrol threshold
p2377
Cascade control - interlock time
Define interlock time
p2378
Cascade control - connect/disconnect speed
Defining the speed for the main drive after connecting/disconnecting a motor