EasyManua.ls Logo

Siemens SINAMICS G120 - Page 70

Siemens SINAMICS G120
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
Power Module PM240
70 Hardware Installation Manual, 07/2009, A5E00807525B AD
Power Module specifications
CAUTION
High Overload (HO) and Light Overload (LO) input currents
The input current at the rated operating point - applies for the short-circuit voltage of the line
supply V
k
= 1% referred to the rated Power Module power and a rated line supply voltage of
400 V without a line reactor. If a line reactor is used, the specified values are reduced.
NOTICE
UL certified Fuses must be used
In order that the system is in compliance with UL, UL certified fuses, circuit-breaker or self
protected combination motor controller must be used.
Table 6- 3 Frame Sizes A, 3 AC 380 V … 480 V, ± 10%
Order No. unfiltered 6SL3224- 0BE13-7UA0 0BE15-5UA0 0BE17-5UA0
kW 0.37 0.55 0.75 Rated power based on HO-
loading
hp 0.5 0.75 1
Power loss kW 0.097 0.099 0.102
Rated input current (HO) A 1.6 2.0 2.5
Rated output current (HO) A 1.3 1.7 2.2
Rated input current (LO) A 1.7 2.1 2.6
Rated output current (LO) A 1.3 1.7 2.2
Fuse A 10 10 10
l/s 4.8 4.8 4.8 Required cooling air flow
CFM 10 10 10
mm
2
1.0 … 2.5 1.0 … 2.5 1.0 … 2.5 Input cable /
Output cable
AWG 18 … 14 18 … 14 18 … 14
kg 1.2 1.2 1.2 Weight
lb 2.6 2.6 2.6