Technical specifications
Power Module PM240
Hardware Installation Manual, 07/2009, A5E00807525B AD
71
Table 6- 4 Frame Sizes A, 3 AC 380 V … 480 V, ± 10%
Order No. unfiltered 6SL3224- 0BE21-1UA0 0BE21-5UA0
kW 1.1 1.5 Rated power based on HO-
loading
hp 1.5 2
Power loss kW 0.108 0.114
Rated input current (HO) A 3.8 4.8
Rated output current (HO) A 3.1 4.1
Rated input current (LO) A 3.9 4.9
Rated output current (LO) A 3.1 4.1
Fuse A 10 10
l/s 4.8 4.8 Required cooling air flow
CFM 10 10
mm
2
1.0 … 2.5 1.0 … 2.5 Input cable /
Output cable
AWG 18 … 14 18 … 14
kg 1.2 1.2 Weight
lb 2.6 2.6
Table 6- 5 Frame Sizes B, 3 AC 380 V … 480 V, ± 10%
filtered 0BE22-2AA0 0BE23-0AA0 0BE24-0AA0
Order No.
unfiltered
6SL3224-
0BE22-2UA0 0BE23-0UA0 0BE24-0UA0
kW 2.2 3 4 Rated power based on HO-
loading
hp 3 4 5
Power loss kW 0.139 0.158 0.183
Rated input current (HO) A 7.6 10.2 13.4
Rated output current (HO) A 5.9 7.7 10.2
Rated input current (LO) A 7.6 10.2 13.4
Rated output current (LO) A 5.9 7.7 10.2
Fuse A 16 16 20
l/s 24 24 24 Required cooling air flow
CFM 50 50 50
mm
2
1.5 … 6.0 1.5 … 6.0 1.5 … 6.0 Input cable /
Output cable
AWG 16 … 10 16 … 10 16 … 10
kg 4.3 4.3 4.3 Weight
lb 9.5 9.5 9.5