5.5.8 Identify motor data
Identify motor data
WARNING
Unexpected machine motion while the motor data identification is in progress
The stationary measurement can turn the motor a number of revolutions. The rotating
measurement accelerates the motor up to the rated speed. Secure dangerous machine parts
before starting motor data identification:
Before switching on, ensure that nobody is working on the machine or located within its
working area.
Secure the machine's working area against unintended access.
Lower suspended loads to the floor.
Preconditions
You selected a method of motor data identification during quick commissioning, e.g.
measurement of the motor data while the motor is stationary.
When quick commissioning is complete, the inverter issues alarm A07991.
The motor has cooled down to the ambient temperature.
An excessively high motor temperature distorts the results of motor data identification.
The PC and inverter are connected to each other online.
Procedure with STARTER
To initiate motor data identification and optimize the motor control, proceed as follows:
1. Open the control panel.
Figure 5-21 Control panel
2. Assume master control for the inverter.
3. Set the "Enable signals"


Commissioning
5.5 Quick commissioning with a PC
Converter with the CU230P-2 Control Units
186 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE