Table 10-56 PM240-2, PT, Frame Size C, 3-ph. AC 380 V … 480 V
Article number without filter
Article number with filter
6SL3211-1PE23-3UL0
6SL3211-1PE23-3AL0
LO base load power 15.0 kW
LO base load input current 39.9 A
LO base load output current 32.0 A
HO base load power 11.0 kW
HO base load input current 36.0 A
HO base load output current 26.0 A
Fuse according to IEC
Fuse according to UL, class J
3NA3820 (50 A)
50 A
Power loss 0.37 kW
1)
Required cooling air flow 18.5 l/s
Weight without filter 5.8 kg
Weight with filter 6.3 kg
1) approx. 0.3 kW through the heatsink
Table 10-57 PM240-2, IP20, Frame Size D, 3-ph. AC 380 V … 480 V
Article number without filter
Article number with filter
6SL3210-1PE23-8UL0
6SL3210-1PE23-8AL0
6SL3210-1PE24-5UL0
6SL3210-1PE24-5AL0
6SL3210-1PE26-0UL0
6SL3210-1PE26-0AL0
LO base load power 18.5 kW 22 kW 30 kW
LO base load input current 36 A 42 A 57 A
LO base load output current 38 A 45 A 60 A
HO base load power 15 kW 18.5 kW 22 kW
HO base load input current 33 A 38 A 47 A
HO base load output current 32 A 38 A 45 A
Fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NA3822 (63 A)
60 A
3NA3824 (80 A)
70 A
3NA3830 (100 A)
90 A
Power loss without filter 0.57 kW 0.70 kW 0.82 kW
Power loss with filter 0.58 kW 0.71 kW 0.83 kW
Required cooling air flow 55 l/s 55 l/s 55 l/s
Weight without filter 16 kg 16 kg 17 kg
Weight with filter 17.5 kg 17.5 kg 18.5 kg
Technical data
10.6 Technical data, PM240-2 Power Module
Converter with the CU230P-2 Control Units