2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
116 List Manual (LH11), 01/2016, A5E33839529
Description: Sets the scaling characteristic for the analog outputs.
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 1st value pair of the
characteristic.
Index: [0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Dependency: The unit of this parameter (V or mA) depends on the analog output type.
Refer to: p0776
Notice: This parameter is automatically overwritten when changing p0776 (type of analog outputs).
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the scaling characteristic for the analog outputs.
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 2nd value pair of the characteristic.
Index: [0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Dependency: Refer to: p0776
Notice: This parameter is automatically overwritten when changing p0776 (type of analog outputs).
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the scaling characteristic for the analog outputs.
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 2nd value pair of the
characteristic.
Index: [0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Dependency: The unit of this parameter (V or mA) depends on the analog output type.
Refer to: p0776
Notice: This parameter is automatically overwritten when changing p0776 (type of analog outputs).
Note: The parameters for the characteristic do not have a limiting effect.
p0778[0...1] CU analog outputs characteristic value y1 / CU AO char y1
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9572
Min Max Factory setting
-20.000 [V] 20.000 [V] 0.000 [V]
p0779[0...1] CU analog outputs characteristic value x2 / CU AO char x2
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9572
Min Max Factory setting
-1000.00 [%] 1000.00 [%] 100.00 [%]
p0780[0...1] CU analog outputs characteristic value y2 / CU AO char y2
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9572
Min Max Factory setting
-20.000 [V] 20.000 [V] 20.000 [V]