2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
352 List Manual (LH11), 01/2016, A5E33839529
Description: Sets the signal source for command 3 for the two-wire control/three-wire control.
Dependency: Refer to: p0015, p3330, p3331, r3333, p3334
Note: The mode of operation of this binector input is dependent on the wire control set in p0015.
Description: Displays the control word for the two wire control/three wire control.
The control signals are dependent on the wire control set in p0015 and the signal states at the digital inputs.
Dependency: Refer to: p0015, p3330, p3331, p3332, p3334
Description: Sets the two wire control/three wire control.
Value: 0: No wire control
1: Two wire control clockwise/counterclockwise 1
2: Two wire control clockwise/counterclockwise 2
3: Three wire control enable clockwise/counterclockwise
4: Three wire control enable ON/reversing
Dependency: Refer to: p0015, p3330, p3331, p3332, r3333
Note: This value depends on the wire control set in p0015.
Description: The friction characteristic is defined by 10 value pairs.
This parameter specifies the n coordinate of the 1st value pair of the friction characteristic.
Dependency: Refer to: p3830, p3845
p3332[0...n] BI: 2/3 wire control command 3 / 2/3 wire cmd 3
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 2273
Min Max Factory setting
- - 0
r3333.0...3 CO/BO: 2/3 wire control control word / 2/3 wire STW
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2272, 2273
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON Yes No -
01 Reversing Yes No -
02 ON inverted Yes No -
03 Reversing inverted Yes No -
p3334 2/3 wire control selection / 2/3 wire select
Access level: 4 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2272, 2273
Min Max Factory setting
0 4 0
p3820[0...n] Friction characteristic value n0 / Friction n0
Access level: 2 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Func. diagram: 7010
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 15.00 [rpm]