2 Parameters
2.2 List of parameters
Description: Display and connector output for the status word of the compound braking and DC quantity control.
Dependency: Refer to: p3856
Description: Exits quick commissioning (p0010 = 1) with automatic calculation of all parameters of all existing drive data sets that
depend on the entries made during quick commissioning.
p3900 = 1 initially includes a parameter reset (factory setting, the same as p0970 = 1) for all parameters of the drive
object; however, without overwriting the entries made during the quick commissioning.
The interconnections of PROFIBUS PZD telegram selection (p0922) and the interconnections via p15 and p1500 are
re-established and all of the dependent motor, open-loop and control-loop control parameters are calculated
(corresponding to p0340 = 1).
p3900 = 2 includes the restoration of the interconnections of PROFIBUS PZD telegram selection (p0922) and the
interconnections via p15 and p1500 and the calculations corresponding to p0340 = 1.
p3900 = 3 only includes the calculations associated with the motor, open-loop and closed-loop control parameters
corresponding to p0340 = 1.
Value: 0: No quick parameterization
1: Quick parameterization after parameter reset
2: Quick parameterization (only) for BICO and motor parameters
3: Quick parameterization for motor parameters (only)
Notice: After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note: When the calculations have been completed, p3900 and p0010 are automatically reset to a value of zero.
When calculating motor, open-loop and closed-loop control parameters (such as for p0340 = 1) parameters
associated with a selected Siemens catalog motor are not overwritten.
If a catalog motor has not been selected (p0300), then the following parameters are reset with p3900 > 0 in order to
restore the situation that applied when commissioning the drive for the first time:
induction motor: p0320, p0352, p0362 ... p0369, p0604, p0605, p0626 ... p0628
synchronous motor: p0326, p0327, p0352, p0604, p0605
Description: Displays the commissioning steps that have been carried out.
r3859.0 CO/BO: Compound braking/DC quantity control status word / Comp-br/DC_ctr ZSW
PM240 Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 6797
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Compound braking active Yes No -
p3900 Completion of quick commissioning / Compl quick_comm
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(1) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 3 0
r3925[0...n] Identification final display / Ident final_disp
Access level: 3 Calculated: p0340 = 1 Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Motor/control parameters calculated (p0340
= 1, p3900 > 0)
Yes No -
02 Motor data identification carried out at
standstill (p1910 = 1)
Yes No -