SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
437
2 Parameters
2.2 List of parameters
Description: Display and BICO output for the Safety Integrated status on the drive (processor 1 + processor 2).
Note: This status is formed from the AND operation of the relevant status of the two monitoring channels.
Description: The parameter is used for diagnostics.
Note: For bit 00 = 1:
At least one Safety parameter has been changed that will only take effect after a POWER ON.
For bit 01 = 1:
Safety functions (basic functions or extended functions) have been enabled and are active.
For bit 02 = 1:
A safety-relevant component has been replaced. Data save required (p0977 = 1 or p0971 = 1 or "copy RAM to
ROM").
r9773.0...31 CO/BO: SI status (processor 1 + processor 2) / SI status P1+P2
PM230_STO
PM240
PM250
PM260
CU240E-2
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 2 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2804
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 STO selected in drive Yes No 2804
01 STO active in drive Yes No 2804
30 PM terminals switch-off signal paths must
be tested
Yes No -
31 Switch-off signal paths must be tested Yes No 2810
r9776 SI diagnostics / SI diag
PM230_STO
PM240
PM250
PM260
CU240E-2
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Safety parameter changed POWER ON
required
Yes No -
01 Safety functions enabled Yes No -
02 Safety component replaced and data save
required