SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
833
4 Faults and alarms
4.2 List of faults and alarms
F07563 (A) Drive encoder: XIST1_ERW configuration incorrect
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Reaction: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Acknowledge: IMMEDIATELY (POWER ON)
Cause: An incorrect configuration was identified for the "Absolute position for incremental encoder" function.
Fault value (r0949, interpret decimal):
Fault cause:
1 (= 01 hex):
The "Absolute value for incremental encoder" function is not supported (r0459.13 = 0).
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
yyxx dec: yy = fault cause, xx = encoder data set
Remedy: For fault value = 1:
- upgrade the Sensor Module firmware version.
- check the mode (p4652 = 1, 3 requires the property r0459.13 = 1).
F07754 Drive: Incorrect shutoff valve configuration
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Reaction: OFF2
Acknowledge: IMMEDIATELY (POWER ON)
Cause: An incorrect shutoff valve configuration was detected.
Fault value (r0949, interpret decimal):
100:
Enable Safety Integrated (p9601/p9801), but p0218.0 = 0 (shutoff valve not available).
101:
The manipulated variable inhibit time is set less than the wait time to evaluate the feedback signal contacts when
switching on the shutoff valve (p0230 < p9625[0]/p9825[0]).
102:
The manipulated variable inhibit time is set less than the wait time to evaluate the feedback signal contacts when
switching off the shutoff valve (p0230 < p9625[1]/p9825[1]).
Remedy: For fault value = 100:
Check the enable of Safety Integrated and the shutoff valve (p9601/p9801, p0218.0).
For fault value = 101:
Set the manipulated variable inhibit time higher than the wait time to evaluate the feedback signal contacts when
switching on the shutoff valve (p0230 > p9625[0]/p9825[0]).
For fault value = 102:
Set the manipulated variable inhibit time higher than the wait time to evaluate the feedback signal contacts when
switching off the shutoff valve (p0230 > p9625[1]/p9825[1]).
See also: p0230 (Drive filter type motor side)
F07800 Drive: No power unit present
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The power unit parameters cannot be read or no parameters are stored in the power unit.
Note:
This fault also occurs if an incorrect topology was selected in the commissioning software and this parameterization
is then downloaded to the Control Unit.
See also: r0200 (Power unit code number actual)
Remedy: - carry out a POWER ON (switch-off/switch-on) for all components.
- check the power unit and replace if necessary.
- check the Control Unit, and if required replace it.
- after correcting the topology, the parameters must be again downloaded using the commissioning software.