Switching the motor on after an internal event
Procedure
To switch the motor on after an internal event while SDI is active, proceed as follows:
1. Deselect the SDI function.
2. Issue an OFF1 command (ON/OFF1 = 0).
3. Acknowledge the internal event in one of the following ways:
Fail-safe acknowledgment using PROFIsafe control word 0, bit 7 = 0 → 1 → 0
Fail-safe acknowledge signal via a fail-safe digital input: F‑DI = 0 → 1 → 0.
Select the STO function and deselect again (PROFIsafe control word 0, bit 0 or F-DI).
1 → 0 → 1).
Select the SS1 function and deselect again (PROFIsafe control word 0, bit 1 or F-DI).
1 → 0 → 1).
Switch off the power supply voltage of the inverter and switch on again.
4. Acknowledge the inverter with the "standard" acknowledge signal.
5. Switch on the motor (ON/OFF1 = 1).
You have acknowledged the internal event and switched on the motor again.

Operation
6.8 Safe Direction (SDI)
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD 291