Commissioning
4.2 Commissioning with BOP-2 operator panel
CU240B-2 and CU240E-2 Control Units
24 Compact Operating Instructions, 04/2015, A5E35792002B AA
9.
Select the application:
OP LOOP
Recommended setting for standard applications.
CL LOOP
Recommended setting for applications with short ramp
-
up and ramp
-down times. This setting is not suitable for
hoisting gear and cranes/lifting gear.
HVY LOAD
Recommended setting for applications with a high break
loose torque.
10.
Select the default setting for the i
nterfaces of the inverter that is suita-
ble for your application. The available default settings can be found in
the operating instructions, see: Manuals for your inverter (Page 31).
11.
Minimum and maximum motor speed
12.
13.
Motor ramp
-up time
14.
Motor ramp
-down time
15.
Ramp
-down time for the OFF3 command
16.
Motor data identification
Select the method which the inverter uses to measure the data of the
connected motor:
OFF
Motor data is not measured.
ST RT OP
Recommended setting: Measure the motor data at stan
d-
still and with the motor rotating.
STILL OP
Me
asure the motor data at standstill.
Select this setting if the motor cannot rotate freely
for
example, if the traversing range is mechanically limited.
17.
Com
plete the basic commissioning:
17.1.
Switch over the display using an arrow key: nO YES
17.2.
Press the OK key.
You have entered all of the data that is necessary for the basic commissioning of your
inverter.