List of Parameters
Parameters
1-333
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Selecting the USB functionality.
Value: 1: USS commissioning via the virtual COM port
2: Only memory access
3: USB commissioning and memory access
Note: COMM: Commissioning.
A change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
Description: Sets the enable signals for the safe motion monitoring.
Dependency: Refer to: p9501
Refer to: F01682, F01683
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: For bit 30 = 1, PROFIsafe telegram 900 must be configured in the F host.
A change only becomes effective after a POWER ON.
F-DI: Failsafe Digital Input
SDI: Safe Direction (safe motion direction)
SLS: Safely-Limited Speed
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
p8999 USB functionality / USB functionality
Access level: 4 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
1 3 3
p9301 SI Motion enable safety functions (processor 2) / SI Mtn enable P2
PM240
PM250
PM260
CU240E-2 DP F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - 0000 0000 0000 0000 0000 0000
0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Enable SLS Enable Inhibit -
16 Enable SSM hysteresis and filtering Enable Inhibit 2860
17 Enable SDI Enable Inhibit 2861
30 Enable F-DI in PROFIsafe telegram 900 Enable Inhibit -