Parameters
List of Parameters
1-354
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the SLS-specific stop response for the function "Safely-Limited Speed" (SLS).
These settings apply to the individual limit values for SLS.
Value: 0: STOP A
1: STOP B
Index: [0] = Limit value SLS1
[1] = Limit value SLS2
[2] = Limit value SLS3
[3] = Limit value SLP4
Dependency: Refer to: p9531
Note: SLS: Safely-Limited Speed
Description: Sets the tolerance for the function "Safe motion direction" (SDI). This motion in the monitored direction is still per-
missible before an alarm is initiated.
Dependency: Refer to: p9565, p9566
Refer to: C01716
Note: SDI: Safe Direction (safe motion direction)
Description: Sets the delay time for the function "Safe motion direction" (SDI). When selecting the SDI function, motion in the
monitored direction is permissible as a maximum for this time; this means that this time can be used for braking
existing motion.
Dependency: Refer to: p9564, p9566
Refer to: C01716
Note: SDI: Safe Direction (safe motion direction)
p9563[0...3] SI Motion SLS-specific stop response (processor 1) / SI Mtn SLS stop P1
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 1 0
p9564 SI Motion SDI tolerance (processor 1) / SI Mtn SDI tol P1
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0.001 [°] 360.000 [°] 12.000 [°]
p9565 SI Motion SDI delay time (processor 1) / SI Mtn SDI t P1
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0.00 [ms] 600000.00 [ms] 100.00 [ms]