Function diagrams
Communication
2-538
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Fig. 2-34 2454 – ZSW3 status word interconnection (p2038 = 0)
- 2454 -
Function diagram
87654321
FP_2454_97_61.vsd
PROFIdrive / PROFIBUS
G120 CU230P-2 DP
13.12.2010 V4.4
ZSW3 status word interconnection (p2038 = 0)
<1>
ZSW3.0
ZSW3.1
ZSW3.2
ZSW3.3
ZSW3.4
ZSW3.5
ZSW3.6
ZSW3.8
ZSW3.9
ZSW3.11
ZSW3.12
ZSW3.13
ZSW3.14
ZSW3.15
ZSW3.7
ZSW3.10
p2051[3] = r0053
[2511.7]
[2511.7]
[2511.7]
[2511.7]
[2511.7]
[2511.7]
[2511.7]
[2511.7]
[2511.7]
[2511.7]
-
-
-
[2511.7]
[2511.7]
-
-
-
-
-
<1>
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Signal sources for ZSW3 im Interface Mode SINAMICS (p2038 = 0)
Signal
Meaning
Interconnection
parameters
[Function diagram]
internal status word
[Function diagram]
signal source
Inverted
Used in telegrams 350.
1 = DC brake active
0 = DC brake not active
1 = |n_act| > p1226 (n_standstill)
1 = |n_act| > p1080 (n_min)
1 = I_act >= p2170
1 = |n_act| > p2155
1 = |n_act| <= p2155
1 = |n_act| >= r1119 (f_set)
1 = Vdc <= p2172
1 = Vdc > p2172
1 = Ramping finished
1 = Techn. contr. out at lower limit
1 = Techn. contr. out at upper limit
Reserved
Reserved
Reserved
Reserved
[7017.5]
[2534.7]
[2534.7]
[2534.7]
[2534.7]
[2534.7]
[2534.7]
[2534.7]
[2534.7]
[3080.7]
[7958.7]
[7958.7]