Additional settings:
• Differential pressure control using the technology controller
• Technological unit: p0595 = 1 (%), reference variable: p0596 = 1
• Default setting of the technology controller:
– Enable: p2200 = 1
– Fixed value 1: p2201 = 50 %
– Ramp-up/down time for setpoint: p2257 = p2258 = 30 s
– Ramp-up/down time for controller output: p2293 = 30 s
– Upper and lower limits, actual value: p2267 = 120 %, p2268 = -10 %
– Actual value filter time constant: p2265 = 10 s
– Proportional gain K
P
, integral time T
I
, differentiation time constant T
D
: p2280 (K
P
) = 1,
p2285 (T
I
) = 30 s, p2274 (T
D
) = 0 s
• "Flying restart" is enabled: p1200 = 1
• Automatic restart is active. After a power failure, the inverter automatically acknowledges possible
faults and switches on the motor: p1210 = 26