Installing
3.5 Default setting of the interfaces
CU230P-2 Control Units
24 Compact Operating Instructions, 01/2017, A5E38815802B AA
Default setting 104: "ESM stairwell pressure control"
DO 0: p0730, …, DO 2: p0732
AO 0: p0771[0], AO 1: p0771[1]
DI 0: r0722.0
AI 0: r0755[0]
Additional settings:
Pressure control using the technology controller
Analog inputs smoothing time constant: p0753 = 500 ms
Technological unit: p0595 = 1 (%), reference variable: p0596 = 1
Default setting of the technology controller:
Enable: p2200 = 1
Fixed value 1: p2201 = 40 %
Ramp-up/down time for setpoint: p2257 = p2258 = 30 s
Ramp-up/down time for controller output: p2293 = 30 s
Upper and lower limits, actual value: p2267 = 120 %, p2268 = -10 %
Actual value filter time constant: p2265 = 10 s
Proportional gain K
P
, integral time T
I
, differentiation time constant T
D
: p2280 (K
P
) = 1.2,
p2285 (T
I
) = 25 s, p2274 (T
D
) = 0 s
Technology controller minimum limiting p2292 = 30 %
Technology controller output signal start value p2302 = 35 %
"Flying restart" is enabled: p1200 = 1
Automatic restart is active. After a power failure, the inverter automatically acknowledges possible
faults and switches on the motor: p1210 = 26
Designation in the BOP-2: P_F Stw