Installing
3.5 Default setting of the interfaces
CU230P-2 Control Units
30 Compact Operating Instructions, 01/2017, A5E38815802B AA
AO 0: p0771[0], AO 1: p0771[1] DI 0: r0722.0, DI 2: r0722.2 AI 0: r0755[0]
Additional settings:
• CO
2
control using the technology controller
• Analog inputs smoothing time constant: p0753 = 500 ms
• Technological unit: p0595 = 1 (%), reference variable: p0596 = 1
• Default setting of the technology controller:
– Enable: p2200 = 1
– Fixed value 1: p2201 = 50 %
– Fixed value 3: p2203 = 10 %
– Technology controller setpoint 1: p2253 = r2224 (active fixed value)
– Ramp-up/down time for setpoint: p2257 = p2258 = 30 s
– Upper and lower limits, actual value: p2267 = 120 %, p2268 = -10 %
– Actual value filter time constant: p2265 = 10 s
– Technology controller system deviation inversion: p2306 = 1
• "Flying restart" is enabled: p1200 = 1
• Automatic restart is active. After a power failure, the inverter automatically acknowledges possible
faults and switches on the motor: p1210 = 26