Technical specifications
6.2 Specific technical data
Power Module PM330
72 Hardware Installation Manual, 10/2016, A5E32844552B AD
Tightening torque for line, motor, DC link, and
50 Nm / 443 lbf in 50 Nm / 443 lbf in 50 Nm / 443 lbf in
Dimensions: Width x height x depth (mm)
The line supply must be capable of supplying the minimum short-circuit current so that the fuses trigger and consequen-
tial damage is avoided.
Note: If the minimum short-circuit current is not reached then the tripping time for the fuses increases, and this may
result in consequential damage.
When semiconductor fuses are used, they must be mounted in the same higher construction as the converter.
3)
When connecting a Braking Module with rated power 50 kW, P
20
power 200 kW.