EasyManua.ls Logo

Siemens SINAMICS G120P PM330 - Page 75

Siemens SINAMICS G120P PM330
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
6.2 Specific technical data
Power Module PM330
Hardware Installation Manual, 10/2016, A5E32844552B AD
75
Table 6- 4 PM330, frame size JX, 3-phase 380480 VAC
Article no.
6SL3310-
1PE38-4AA0
1PE38-8AA0
1PE41-0AA0
Rated input current
- for 380/400 V, 40° C
- for 480 V, 40° C
- for 380/400 V, 50° C
- for 480 V, 50° C
870 A
702 A
740 A
596 A
945 A
767 A
803 A
652 A
1061 A
880 A
901 A
748 A
Rated input current DCP/DCN
(for 2/3 of the converter power)
- at 510 V
DC
, 40 °C
- at 650 V
DC
, 40 °C
- at 510 V
DC
, 50 °C
- at 650 V
DC
, 50 °C
715 A
577 A
608 A
490 A
775 A
629 A
659 A
535 A
870 A
722 A
739 A
613 A
Rated output current I
N
- at 380/400 V, 40° C
- at 480 V, 40° C
- at 380/400 V, 50° C
- at 480 V, 50° C
840 A
677 A
714 A
576 A
910 A
739 A
774 A
628 A
1021 A
847 A
868 A
720 A
LO base load power
LO base load input current at 400 V
LO base load output current at 400 V
450 kW
850 A
820 A
500 kW
925 A
890 A
560 kW
1039 A
1000 A
HO base load power
HO base load input current at 400 V
HO base load output current at 400 V
355 kW
696 A
672 A
400 kW
756 A
728 A
450 kW
816 A
786 A
Fuse according to IEC
Manufacturer:
Maximum permissible line short-circuit current I
kmax
Minimum line short-circuit current required I
kmin
1)
2 x 3NE1334-2 //
(2 x 500 A / 690 V)
Siemens AG
≤ 100 kA
> 10.4 kA
2 x 3NE1435-2 //
(2 x 560 A / 690 V)
Siemens AG
≤ 100 kA
> 14.0 kA
2 x 3NE1436-2 //
(2 x 630 A / 690 V)
Siemens AG
≤ 100 kA
> 16.0 kA
Fuse in compliance with UL
2)
Manufacturer:
Minimum line short-circuit current required I
kmin
1)
3NB3350-1KK26
(1000 A/690 V)
Siemens AG
8.6 kA
3NB3351-1KK26
(1100 A/690 V)
Siemens AG
17.0 kA
3NB3352-1KK26
(1250 A/690 V)
Siemens AG
18.0 kA
max. power loss, at I
N
, 40 °C, 400 V
10.418 kW
10.885 kW
12.495 kW
Required cooling air flow
450 l/s
450 l/s
450 l/s
Maximum connectable cross-section of the power
cable
6 x 240 mm
2
6 x 500 kcmil
6 x 240 mm
2
6 x 500 kcmil
6 x 240 mm
2
6 x 500 kcmil
Maximum connectable cross-section of the motor
cable
4 x 240 mm
2
4 x 500 kcmil
8 x 240 mm
2
8 x 500 kcmil
8 x 240 mm
2
8 x 500 kcmil
Maximum connectable cross-section of the DC-link
cable
4 x 240 mm
2
4 x 500 kcmil
4 x 240 mm
2
4 x 500 kcmil
4 x 240 mm
2
4 x 500 kcmil
Recommended cable cross-section for 380 V/400 V
- line cable
- motor cable
3)
4 x 185 mm
2
4 x 150 mm²
4 x 185 mm
2
4 x 185 mm²
4 x 240 mm
2
4 x 240 mm²
Recommended cable cross-section for 480 V
- line cable
- motor cable
3)
4 x 120 mm
2
4 x 120 mm²
4 x 150 mm
2
4 x 150 mm²
4 x 185 mm
2
4 x 150 mm²
Recommended cable cross-section for 380 V/400 V
- DC link infeed (2/3 converter power)
- Braking Module
4)
4 x 120 mm
2
35 mm²
4 x 150 mm
2
35 mm²
4 x 185 mm
2
35 mm²

Table of Contents