Technical specifications
6.2 Specific technical data
Power Module PM330
76 Hardware Installation Manual, 10/2016, A5E32844552B AD
Recommended cable cross-section for 480 V
- DC link infeed (2/3 converter power)
4)
3 x 120 mm
2
3 x 150 mm
2
3 x 185 mm
2
Tightening torque for line, motor, DC link, and
50 Nm / 443 lbf in 50 Nm / 443 lbf in 50 Nm / 443 lbf in
Dimensions: Width x height x depth (mm)
The line supply must be capable of supplying the minimum short-circuit current so that the fuses trigger and consequen-
tial damage is avoided.
Note: If the minimum short-circuit current is not reached, the tripping time for the fuses increases, which may result in
consequential damage.
When semiconductor fuses are used, they must be mounted in the same higher construction as the converter.
The motor cables must be evenly distributed on both connection chambers.
4)
For connection of the Braking Module with rated power of 50 kW, P
20
power of 200 kW.