EasyManua.ls Logo

Siemens SINAMICS G120P PM330 - Page 77

Siemens SINAMICS G120P PM330
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
6.2 Specific technical data
Power Module PM330
Hardware Installation Manual, 10/2016, A5E32844552B AD
77
Table 6- 5 PM330, frame size HX, 3-phase 500 690 VAC, Part 1
Article No.
6SL3310-
1PG33-7AA0
1PG34-0AA0
1PG34-5AA0
Rated input current
- at 500 V, 40 °C
- at 600 V, 40 °C
- at 690 V, 40 °C
- at 500 V, 50 °C
- at 600 V, 50 °C
- at 690 V, 50 °C
383 A
367 A
354 A
326 A
312 A
301 A
416 A
412 A
409 A
354 A
350 A
348 A
471 A
459 A
447 A
400 A
390 A
380 A
Rated input current DCP/DCN
(for 2/3 of the converter power)
- at 675 V
DC
, 40 °C
- at 810 V
DC
, 40 °C
- at 930 V
DC
, 40 °C
- at 675 V
DC
, 50 °C
- at 810 V
DC
, 50 °C
- at 930 V
DC
, 50 °C
314 A
301 A
290 A
267 A
255 A
246 A
341 A
337 A
335 A
290 A
287 A
284 A
385 A
376 A
366 A
328 A
319 A
311 A
Rated output current I
N
- at 500 V, 40 °C
- at 600 V, 40 °C
- at 690 V, 40 °C
- at 500 V, 50 °C
- at 600 V, 50 °C
- at 690 V, 50 °C
368 A
353 A
340 A
313 A
300 A
289 A
400 A
396 A
393 A
340 A
337 A
334 A
453 A
441 A
430 A
385 A
375 A
366 A
LO base load power
LO base load input current at 690 V
LO base load output current at 690 V
315 kW
343 A
330 A
355 kW
401 A
385 A
400 kW
437 A
420 A
HO base load power
HO base load input current at 690 V
HO base load output current at 690 V
250 kW
283 A
272 A
315 kW
327 A
314 A
355 kW
362 A
348 A
Fuse according to IEC
Manufacturer:
Maximum permissible line short-circuit current I
kmax
Minimum line short-circuit current required I
kmin
1)
3NE1333-2
(450 A/690 V)
Siemens AG
≤ 100 kA
> 3.5 kA
3NE1334-2
(500 A/690 V)
Siemens AG
≤ 100 kA
> 4.5 kA
3NE1435-2
(560 A/690 V)
Siemens AG
≤ 100 kA
> 7.0 kA
Fuse in compliance with UL
2)
Manufacturer:
Maximum permissible line short-circuit current I
kmax
Minimum line short-circuit current required I
kmin
1)
3NE1333-2
(450 A/690 V)
Siemens AG
≤ 100 kA
> 3.5 kA
3NE1334-2
(500 A/690 V)
Siemens AG
≤ 100 kA
> 4.5 kA
3NE1435-2
(560 A/690 V)
Siemens AG
≤ 100 kA
> 7.0 kA
max. power loss, at I
N
, 40 °C, 690 V
5.402 kW
6.191 kW
6.884 kW
Required cooling air flow
360 l/s
360 l/s
360 l/s
Maximum connectable cross-section of the line,
motor and DC-link cable
4 x 240 mm
2
4 x 500 kcmil
4 x 240 mm
2
4 x 500 kcmil
4 x 240 mm
2
4 x 500 kcmil
Recommended cable cross-section for 500 V
- line cable
- motor cable
2 x 120 mm
2
2 x 120 mm²
2 x 150 mm
2
2 x 120 mm²
2 x 185 mm
2
2 x 150 mm²
Recommended cable cross-section for 690 V
- line cable
- motor cable
2 x 120 mm
2
2 x 95 mm²
2 x 150 mm
2
2 x 120 mm²
2 x 185 mm
2
2 x 150 mm²

Table of Contents

Related product manuals