Technical specifications
6.2 Specific technical data
Power Module PM330
Hardware Installation Manual, 10/2016, A5E32844552B AD
81
Table 6- 7 PM330, frame size JX, 3 AC 500 V … 690 V
Rated input current
- at 500 V, 40 °C
- at 600 V, 40 °C
- at 690 V, 40 °C
- at 500 V, 50 °C
- at 600 V, 50 °C
596 A
578 A
555 A
506 A
492 A
679 A
647 A
618 A
577 A
550 A
753 A
720 A
690 A
640 A
612 A
Rated input current DCP/DCN
(for 2/3 of the converter power)
- at 675 V
DC
, 40 °C
- at 810 V
DC
, 40 °C
- at 930 V
DC
, 40 °C
- at 675 V
DC
, 50 °C
- at 810 V
DC
, 50 °C
DC
495 A
474 A
456 A
420 A
403 A
557 A
531 A
507 A
473 A
451 A
617 A
590 A
566 A
525 A
502 A
Rated output current I
N
- at 500 V, 40 °C
- at 600 V, 40 °C
- at 690 V, 40 °C
- at 500 V, 50 °C
- at 600 V, 50 °C
581 A
557 A
535 A
494 A
473 A
654 A
623 A
595 A
555 A
530 A
725 A
693 A
665 A
616 A
589 A
LO base load power
LO base load input current at 690 V
LO base load output current at 690 V
500 kW
540 A
520 A
560 kW
602 A
580 A
630 kW
675 A
650 A
HO base load power
HO base load input current at 690 V
HO base load output current at 690 V
450 kW
461 A
444 A
500 kW
494 A
476 A
560 kW
552 A
532 A
Fuse according to IEC
Manufacturer:
Maximum permissible line short-circuit current I
kmax
Minimum line short-circuit current required I
kmin
1)
3NE1437-2
(710 A/690 V)
Siemens AG
≤ 100 kA
3NE1438-2
(800 A/690 V)
Siemens AG
≤ 100 kA
3NE1448-2
(850 A/690 V)
Siemens AG
≤ 100 kA
Fuse in compliance with UL
2)
Manufacturer:
Maximum permissible line short-circuit current I
kmax
Minimum line short-circuit current required I
kmin
1)
3NE1437-2
(710 A/690 V)
Siemens AG
≤ 100 kA
3NE1438-2
(800 A/690 V)
Siemens AG
≤ 100 kA
3NE1448-2
(850 A/690 V)
Siemens AG
≤ 100 kA
max. power loss, at I
N
, 40 °C, 690 V
Required cooling air flow
Maximum connectable cross-section of the power
6 x 240 mm
2
6 x 240 mm
2
6 x 240 mm
2
Maximum connectable cross-section of the motor
4 x 240 mm
2
4 x 240 mm
2
4 x 240 mm
2
Maximum connectable cross-section of the DC link
4 x 240 mm
2
4 x 240 mm
2
4 x 240 mm
2