9.3.3 Correcting an unsuccessful firmware upgrade or downgrade
How does the inverter signal an unsuccessful upgrade or downgrade?
5'<
%)
The inverter signals an unsuccessful firmware upgrade or downgrade
by a quickly flashing LED RDY and the lit LED BF.
Correcting an unsuccessful upgrade or downgrade
You can check the following to correct an unsuccessful firmware upgrade or downgrade:
Does the firmware version of your inverter fulfill the preconditions?
For an upgrade, as a minimum V4.5.
For a downgrade, as a minimum V4.6.
Have you correctly inserted the card?
Does the card contain the correct firmware?
Repeat the appropriate procedure.
Corrective maintenance
9.3 Firmware upgrade and downgrade
Converter with the CU230P-2 Control Units
432 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE